How Loud a Heat Pump Is, in Numbers You Can Check
A cold-climate heat pump's outdoor unit is rated at about 51 to 58 dB(A) of sound pressure in Mitsubishi's 2025 Hyper-Heat multi-zone submittals, 2 dB louder in heating than in cooling. Toronto's noise bylaw caps a residential air conditioner or similar device at 45 dB(A) overnight and 50 dB(A) by day, measured near the neighbour's building, so the spec number alone never settles it. What matters is how much of that number survives the trip across the side yard.
That trip is arithmetic. For a small outdoor unit in open air, sound pressure drops about 6 dB each time the distance doubles. A unit rated 58 dB(A) at a 1 metre reference is near 46 dB(A) at 4 metres before any reflections are counted, near 49 dB(A) once the house wall behind it reflects sound toward the neighbour, and near 52 dB(A) in an inside corner. The difference between passing and failing a 45 dB(A) night limit is often one wall and a few metres.
The Two Decibel Figures on a Spec Sheet
Outdoor-unit literature uses two different quantities, and mixing them up is the most common reason homeowners and contractors talk past each other.
Sound pressure level (Lp) is what a microphone reads at one spot. It depends on distance, on the room or yard the unit sits in, and on where the microphone is. The Mitsubishi figures above are sound pressure levels. The submittal gives the operating conditions (cooling at 95°F outdoors, heating at 47°F outdoors) but does not print the measurement distance on the page, which means the number tells you how two Mitsubishi units compare with each other and not, by itself, what a neighbour hears.
Sound power level (Lw) describes the total acoustic energy the unit radiates, independent of distance. Some data sheets give sound power instead of, or as well as, sound pressure, and a sound power figure always looks higher than a sound pressure figure taken a metre or more from the same machine, for reasons that are geometry, not loudness. A sound power value has to be converted before it can be compared with a bylaw limit. The conversion, for a unit sitting on the ground in open air, is:
Lp = Lw + 10 × log10(Q ÷ (4 × π × r²))
where r is the distance in metres and Q is the directivity factor: 2 for a unit on open ground (half the sphere is blocked by the ground), 4 for a unit on the ground against one wall, 8 for one tucked into an inside corner. At 1 metre with Q = 2, that formula subtracts 8 dB from the sound power figure. Against a wall (Q = 4) it subtracts 5 dB. So a condenser with a sound power of 72 dB(A) produces about 64 dB(A) one metre away in the open and about 67 dB(A) one metre away against the house.
A-weighting is the "(A)" in dB(A). It discounts low frequencies roughly the way human hearing does at moderate levels. Every bylaw in the table further down is written in A-weighted decibels, which is convenient for comparison and also a blind spot: a compressor hum or a fan's blade-pass tone can be annoying through a closed window while adding very little to the A-weighted total.
A practical consequence: when a contractor says "this unit is 56 decibels", ask which of the three they mean. Sound pressure at what distance and in which mode, or sound power. The answer changes the setback by a factor of two or three.
Published Ratings for Cold-Climate Outdoor Units
The table lists the outdoor-unit sound figures from three current manufacturer submittals read on November 13, 2026. They are rated-condition numbers from one brand. Each manufacturer tests its own way, so a figure from another brand's sheet is less comparable with these than these are with each other.
| Outdoor unit (Mitsubishi Hyper-Heat, multi-zone) | Zones | Rated heating capacity at 47°F, non-ducted | Sound pressure, cooling | Sound pressure, heating | Cabinet W x D x H | Lowest heating intake temperature |
|---|---|---|---|---|---|---|
| MXZ-2D20NLHZ | up to 2 | 22,000 Btu/h | 51 dB(A) | 53 dB(A) | 950 x 330 x 796 mm | -12°F (-24°C) |
| MXZ-3D24NLHZ | up to 3 | 25,000 Btu/h | 56 dB(A) | 58 dB(A) | 950 x 330 x 796 mm | -12°F (-24°C) |
| MXZ-3D30NLHZ | up to 3 | 28,600 Btu/h | 56 dB(A) | 58 dB(A) | 950 x 330 x 796 mm | -12°F (-24°C) |
All three rows come from Mitsubishi Electric's US submittals coded METUS_2025-03. Cooling is rated at 95°F outdoors and heating at 47°F outdoors; neither sheet prints a measurement distance or a sound power level. A 2022 Mitsubishi Electric Sales Canada submittal for an older three-zone model, the MXZ-3C30NAHZ3-U1, lists 54 dB(A) in cooling and adds a line the US sheets leave out: "Rated data is determined at a fixed compressor speed." That sentence is the key to reading every row above. The rating is one speed, chosen by the test procedure, not the loudest speed the inverter can reach.
Three patterns are worth reading out of the table directly:
- Heating is louder than cooling in every row. In each of these submittals the heating figure is 2 dB above the cooling figure. In a cold climate the heating figure is the one that matters, because the unit runs longest, at the highest compressor speed, on winter nights when bedroom windows face it and background traffic noise is lowest.
- The same box can be 5 dB louder. All three units share a 950 x 330 x 796 mm cabinet, yet the three-zone models are rated 5 dB above the two-zone model in both modes. Between the two three-zone models the rating does not move at all, even though the larger one is rated for 3,600 Btu/h more heating. By the distance arithmetic below, 5 dB is the difference between a unit 4 metres from a window and one about 7 metres away. Cabinet size says nothing about sound; the submittal line does.
- The rated point is not the loudest point. Heating ratings are taken at 47°F (8.3°C). On a -15°C night the same inverter compressor runs much faster to hold capacity, and the fan follows it. No submittal in the table publishes a sound level at low ambient temperature, so the rated figure is a floor for winter operation, not a ceiling.
If a quote names a unit that is not in the table, the same numbers are usually on page one or two of its submittal, in the outdoor-unit column labelled "Sound Pressure Level" or "Sound Level". Ask for that page with the quote. Our cold-climate heat pump performance data page covers the capacity side of the same submittals.