Heat Pump Aux Heat Running Constantly: Normal, Costly, or a Fault?
By EnergyBS Editorial Team | November 13, 2026
Aux heat that runs for hours is normal only when it is colder outside than your heat pump's balance point, which for many houses sits somewhere below freezing. Above about 40°F (4°C), Carrier says long AUX runs may point to a fault. Every hour of strip heat costs its kilowatt rating times your electricity price: a 10 kW strip at the August 2026 US residential average of 18.16 cents per kWh (EIA) costs about $1.82 an hour, three times what the heat pump would spend on the same heat at a coefficient of performance (COP) of 3.
That price gap is why a thermostat stuck on AUX shows up on the bill within a single billing cycle, and why the outdoor temperature at the moment you see the light is the first thing to write down. The same AUX indicator means three different things at 45°F, 25°F and 0°F, and the table below sorts them.
What the AUX light is actually reporting
On a heat pump thermostat, AUX (or AUX HEAT, or a second-stage heat icon) means the thermostat is energizing its auxiliary heat output. In most ducted systems that output switches on electric resistance coils, called heat strips or a heater kit, mounted in the indoor air handler. In a dual fuel system it lights a gas or propane furnace instead, and the cost question changes completely; our dual fuel heat pump cost guide covers that case.
Two features of the light trip people up.
First, AUX normally runs alongside the heat pump, not instead of it. Carrier describes auxiliary heat as automatic: it "runs alongside your heat pump to boost heating power." If the outdoor unit is humming and the fan on top is turning while AUX is lit, the compressor is still doing most of the work and the strips are filling a gap.
Second, AUX is not emergency heat. Emergency heat (EM HEAT, EHEAT) is a mode you select by hand. Carrier's page says it "shuts off the heat pump entirely and uses only the backup heating source," and that you should switch to it only if the heat pump has broken down. A thermostat left on EM after a scare will run the strips all day by design. If your display says EM rather than AUX, switch the mode back to HEAT before reading further.
Symptom plus outdoor temperature: a decision table
Read the outdoor temperature from a weather app or your thermostat's outdoor sensor, then find the row that matches what you see. The temperatures here are reference points from the sources named in the last column, not a universal rule: Carrier states plainly that "there is no single outdoor temperature at which every Carrier heat pump activates auxiliary heat."
| What you see | Outdoor temperature | Most likely cause | Normal or fault | First check | Basis |
|---|---|---|---|---|---|
| AUX on for a few minutes, steam or dripping water at the outdoor unit, then off | Near or below freezing, damp weather | Defrost cycle | Normal | Watch one full cycle; heat should return on its own | Carrier: aux "assists during the defrost cycle" |
| AUX on for 15 to 60 minutes each morning, then off | Any | Recovery from a night setback or a large setpoint jump | Normal by design, but costly | Shrink the setback; check the thermostat's recovery setting | Carrier: aux helps when you raise the setting "by more than 2-3 degrees at once" |
| AUX cycles on and off for hours, house holds the setpoint | Below the house's balance point (often below freezing) | Heat pump capacity has fallen below the house's heat loss | Normal | Confirm the outdoor unit runs the whole time | Carrier: below the "thermal balance point" the heat pump "may need supplemental heat" |
| AUX on most of the day, house sags 2°F or more below setpoint | Well below the balance point | Strips undersized, one strip stage failed, or the heat pump is undersized for the house | Design limit or partial fault | Check the heater kit's breakers; compare kW installed with the design gap | Load and capacity arithmetic (below) |
| AUX on while the outdoor unit sits silent | Any | Compressor locked out by a setting, a tripped outdoor breaker, or a failed outdoor unit | Setting error or fault | Check the compressor lockout temperature and the outdoor disconnect | BPA PTCS sheets (lockout settings) |
| AUX runs for long stretches on mild days | Above about 40°F (4°C) | Dirty filter, refrigerant leak, faulty sensor, or too fast a setpoint increase | Likely fault | Replace the filter, then look at the setpoint schedule | Carrier FAQ, which lists these four |
| AUX still runs above the lockout you thought was set | Above the lockout value | Outdoor sensor not configured, so the lockout never applies | Setting error | Confirm the thermostat shows an outdoor temperature | BPA: Honeywell ISU 130 must be 1 or "strip heat lockout will not function" |
| Display reads EM HEAT or EHEAT | Any | Emergency heat selected by hand | Setting error | Switch the mode to HEAT | Carrier: emergency heat is manual |
| Warm air from the vents and the meter spinning with the thermostat satisfied | Any | Strips energized with no call, such as a heater relay stuck closed | Fault | Turn the system off at the thermostat; if warm air continues, call | Wiring logic; needs a technician to confirm |
The table carries most of the diagnosis. If your case fits rows one to three, the system is working as designed and the decision is about money and settings. Rows four to nine point to a setting or a part.